The increasing integration of photovoltaic (PV) plants in conventional power systems has led to the need to examine the effects of these plants on the system dynamics. In this study, a well-known IEEE-9 bus power system is modified by integrating PV plant in DigSilent Powerfactory environment. Then, 3 transient cases are tested by using PV plant control units designed by Western Electricity Coordinating Council (WECC). The effect of load and line transient disconnections and 3-phase short circuit fault on modified power system are investigated as case-I, case-II, and case-III, respectively. In all cases, two sub-cases are considered according to the location. As a result, comparison of PV system reactive power control methods (RPCM) is analyzed in terms of voltage stability in these 3 cases.
Reactive power control methods IEEE-9 bus power system with large scale PV integration voltage stability 3-phase short circuit fault transient line and load disconnection distance factor